62-814.100 Intent, Findings, Basis of Standards, and Research Needs.
(1) through (3) No change.
(4) Categories of Electrical Facilities. This chapter sets forth three categories of electrical facilities for regulation in regards to the electric and magnetic fields associated with these facilities.
(a) No change.
(b) The second category of electrical facilities is for those which were certified pursuant to Chapter 403, Part Two, Florida Statutes, after April 15, 1988, but before March 21, 1989. These facilities will be subject to specific standards moderated by the individual circumstances of the facility.
(b)(c) No change.
(5) No change.
Specific Authority 403.061(7), 403.523(1) FS. Law Implemented 403.061(30), 403.523(14) FS. History–New 3-21-89, Amended 1-7-93; Formerly 17-274.100, Formerly 17-814.100, Amended_________.
62-814.450 Electric and Magnetic Field Standards.
(1) through (2) No change.
Table of New Transmission Line and Substation Standards
KV Rating |
Property Boundary of new Substation |
Edge of Transmission Line Right-of-Way |
On the Transmission Line Right-of-Way |
< |
2.00 kV/m & 150 milliGauss |
2.00 kV/m & 150 milliGauss |
8 kV/m |
<=500 kV and > 230 kV |
2.00 kV/m & 200 milliGauss [1] |
2.00 kV/m & 200 milliGauss |
10 kV/m |
>500 kV |
5.5 |
5.5 |
15 kV/m |
Footnote 1: Except as provided in (2)(g) and (2)(i).
Specific Authority 403.061(7), 403.523(1) FS. Law Implemented 403.061(30), 403.523(14) FS. History–New 3-21-89, Amended 1-7-93; Formerly 17-274.450, Formerly 17-814.450, Amended ________.